LWCO HYDROLEVEL CG400P

Specifications Model CG400 Power Consumption 2.1 VA Switching Capacity 50 VA Switch Contacts SPDT 15 PSI

Burner circuit contacts open after 15 second delay in a low water condition. Delay prevents short cycling caused by momentary fluctuations in the boiler water level. Automatically reactivates burner circuit 30 seconds after water reaches the probe, allowing optional water feeder to raise water level above the probe. Intermittent Level Test (ILT) feature provides maximum boiler protection by removing power from the burner circuit at set intervals.